"The enclosure is to be self-contained, minimum 42RU up to 47RU with built-in UPS, power distribution, air cooling unit with temperature, humidity, water leakage and smoke sensor monitoring, keypad operated door locks and system management/monitoring front panel display with keypad.
19” Industry standard equipment up to 47U high, 42U is the minimal acceptable rack height.
Self-contained 19” rack fitted with built-in UPS and cooling.
Dimensions: H ~2000mm x 600mm W x minimum 1000mm D
PUE (full Load): 1.2 (optimal)
Input Power: AC 220-240V, 50/60Hz +/-5%
Installation type will be general ground installation
Security: lockable front and rear door. electronic door control from local panel or remote control.
Rack is to be fully supplied with front blanking plates in 1RU, 2 RU, 4RU sizes to ensure rack front is fully sealed for air flow efficiency. Adequate combinations and spares are to be supplied to infill when equipment is inserted.
UPS – o Enclosure UPS rating to be supplied as specified in Goods Schedule as either:
3kVA model, or
5kVA/6kVA model.
o Maximum “User” Equipment Load is to be provided as per chosen model (3kVA or 5kVA/6kVA), UPS capacity rating is to be the available power for user equipment in addition to any UPS power requirements to operate the enclosure subsystems.
o UPS to be of double on-line conversion type with pure sinusoidal wave output.
o Air Conditioning: Power by dedicated minimum 3kVA UPS or as rating required by cooling system
Input Voltage Range: 176-276 without derating (up to 100-276 with derating) o Input Frequency Range: 40-70Hz, 50/60Hz auto selection o Power Selection: 1.0
o Installation: Rackmount, 2RMU or up to 4RMU depending on the UPS capacity requested.
Power Distribution System o Installation Dimensions: Rack mount, 3RMU
o Power Distribution: Mains input and UPS output, lightning protection and maintenance bypass
o PDU: Managed 0RU, plugs to suit Internal Brand Servers and switches, combination minimum 1 x C20 16A, 14 x C13, 4 x C19 Outlets
Cooling and Airflow Management System:
o Total Cooling Capacity: minimum 3.0kW o A/C Total Air Volume: minimum 580m3/h o A/C Power Supply (Voltage): 220 – 240 VAC +/- 5%
o A/C Installation: Rack-mountable, bottom of the enclosure interior, 5RMU o Environmentally friendly refrigerant
Enclosure Subsystem:
o Load Rating: 1500kg"